Is there a return to factory settings in the products?
These features are available in our ECO LITE, ECO HR, ECO PID devices.
Where can I find the Datasheets of the devices?
You can download by entering the FILES section of the product selected from the website.
What should I do to monitor my generator remotely?
First of all, the technical infrastructure must be determined in order to monitor the generator remotely. If there is an ethernet line in the location of the generator, remote monitoring can be provided by installing an ethernet module in the Trans-AMF control panel.
If there is no ethernet line, remote monitoring can be provided by installing a GPRS module in the Trans-AMF device. The GP-enabled model of the Trans-MidiAMF device can also be used. It should not be overlooked that there will be monthly sim card expenses in GPRS monitoring since the devices will be equipped with a sim card.
If monitoring is to be made from a control room located at a location close to the location of the generators, the model of the control panel with RS-485 communication port can also be preferred.
What are your devices that control both temperature and time?
You can provide with our ESM-9944, ESM-9945, ESM-9944-N, ESM-9945-N, Oven Control devices for detailed information.
What are your devices with temperature record keeping feature?
The ability to keep records with all our devices that can communicate with RS-485, to the monitoring feature. With CHANNEL8-N (ability to record flash memory in our USB powered devices), you can keep advanced record in itself with software with HMI operator panels.
Is there an input type selection in ECO PID temperature controllers?
Yes ; Universal temperature sensor type available, can be selected by parameter (TC types and PT-100).
ERM-3770-N npn, how to choose pnp sensor?
Select npn or pnp from the device parameter "in.ty"
How to set ESM-3700-N 4-20ma input, 0-1500 scale
Device parameter "uasl" 4 is selected, "tpol" 0, "tpoh" 1500 are selected
Can the ESM-3710-N Device read PT-100 sensor?
Yeah; ESM-3710-N is fixed calibration, if you specify PT-100 sensor input on order, you can supply the product as fixed PT-100 calibration. Product entry type must be selected in the order.
Is there communication in ESM-3710-N Device?
Yeah; With the Pro-485 communication module, communication can be provided over the device Modbus protocol.
Can we transfer the set parameters on the ESM-3710-N device to another device of the same model?
Yeah; The device can be transferred to the same model device by taking device parameters with the pro-key switch.
Does the ESM-3710-N have a cooling mode?
Yeah; The device can operate as heating and cooling.
Are compressor protection parameters available in ESM-3710-N Cooling mode?
Yeah; Compressor start and stop times and delays can be adjusted.
I do not know the ESM-3710-N password, how can I cancel the password
When the device is encrypted, the "prog" parameter appears when entering the parameters, our factory password is entered with 2111, the "pas" parameter is checked. If the password is not desired, the "pas" parameter is set to 0.
Can ° F (Fahrenheit) be selected on the ESM-3710 N?
° F and ° C can be selected in device parameters.
Why can't I increase the set value of ESM-3710-N above 20 ° C?
Set value limitation parameter "sul" and "suh" values are checked on the device. Example: If the value of "sul" is 10, the set value cannot be set below 10, if the value of "suh" is 18, the set value cannot be set above 18.
ESM-3710-N gives SBR error?
When the sensor cannot read the sensor, it gives SBR (sensor inability to read) warning. When reading the sensor, the temperature value is displayed.
How long is the parameter settings entered in the ESM-3710-N kept in the device processor?
The microprocessor storage feature available on the ESM-3710-N is available, and this nonvolatile memory has a write and read life of approximately 100,000 times.
Can I run buzzer or fan as alarm of ESM-3722 incubator controller?
Yes ; The “Lout” parameter in the parameter settings can be adjusted for temperature, humidity or both temperature and humidity.
The keys on the ESM-3722 do not change the values. What should I do?
When you access the parameters with the OK button and select the PRT (button protection parameter) parameter as 0 (zero), their values are changed.
ESM-3723 SBR1 and SBR2 error
When I add the cable of the humidity and temperature sensor coming out of the device, the ESM-3723 gives the error SBR1 and SBR2. What should I do?
Maximum cable length is 2.5 meters in humidity and temperature sensor supplied with ESM-3723 device. ANNEX cannot be made. Input types are located in the device and sensor order table.
How to set ESM-4900, 4-20ma input, 0.0-16.0 scale
"Issl" 2, "uasl" 4, "dpnt" 1, "ucal" 1, "tpol" 0.0, "tpoh" 16.0 values are entered in the device parameter "pinp" "conf"
Can we choose sensors for ESM-XX10 series devices?
No ; In these series, you have to specify the sensor selection in the order.
Where should we enter the subset value in ESM-XX10 series devices?
Difference value is entered into the “HS1” (Hysteresis) parameter as a subset value. For example, if you want to operate between 100 ° C and 90 ° C; 100 ° C is entered into the set value and “10” is entered into the “HS1” value.
Which temperature sensors can the ESM-XX20 Device read?
Selectable PT-100 can read PT-100 decimal, J, K, S, R and T type Thermocouple sensors.
Where should we enter the subset value in ESM-XX10 series devices?
Difference value is entered into the “HS1” (Hysteresis) parameter as a subset value. For example, if you want to operate between 100 ° C and 90 ° C; 100 ° C is entered into the set value and “10” is entered into the “HS1” value.
What are the outputs of the ESM-XX20 Device?
The device has a standard 2 x Relay and 1 SCR output.
Is there a PID working form in the ESM-XX20 device?
Yes there is, the device can operate as On / Off or PID.
Can user password be set in ESM-XX20 menu settings?
Yes, a 4 digit user password can be created.
Does the ESM-XX20 have a communication option?
No; Our ESM-XX20 series devices do not have a communication option. We have ESM-XX50 series devices for communication.
Does ESM-XX20 series devices have the ability to continue working in case of sensor failure?
Yeah; Percentage output can be selected with Sbou (Sensor break output).
How to choose ESM-4420 PID, how to calculate PID
"Plol" and "pupl" working scale lower and upper limit values are entered in the device parameter "pros", set value is entered into the device, "cnts" pid, tune "yes" is selected in the device parameter "cont"
ESM-4420 It says fixed -200 on my screen, what should I do?
Measure the signal from the sensor. If the correct signal is coming, check the sensor selection from PIN5 parameter within the PROS parameter. Select the type of sensor connected.
How is the sensor selection made in the ESM-XX20 controller? How to connect 2 pin Pt-100?
Connect the 2-pin Pt-100 cables to terminals 1 and 2 in the ESM-XX20 series and bridge the terminal 3 from terminal 2. Then, press the “PSET” button for 5 seconds to switch to the program parameters menu. When the word "PROG" appears on the screen, press the "ASET" button. In the "ProS" parameter displayed, press the "ASET" button again. Press up / right direction button until “rtd0” is written under “PınS” parameter displayed on the screen. Finally, confirm by pressing the "ASET" button. Your sensor type is set to Pt-100. You can switch to the working screen by pressing the “PSET” button twice.
How can I automatically calculate PID on ESM-XX20 series controller?
Enter the Set value you want to fix by pressing the “PSET” button and confirm with “ASET”. Then press and hold the "PSET" button for 5 seconds while on the work screen. Press the "ASET" button while the "ProG" is displayed. Come to the "Cont" parameter with the up / right direction button and press the "ASET" button. Select relay / SSR from “Cout” parameter and press “ASET” button. Select "HEAt" from the "PrtS" parameter and press the "ASET" button. Select "PID" from the "CntS" parameter and press the "ASET" button. Select “YES” parameter in “tunE” parameter and press “ASET” button. You can switch to the working screen by pressing the PSET button twice. “TunE” will flash on the display. This indicates that the PID operation is in progress. When the flashing process is finished, the PID will be completed automatically.
How do we determine the subset (hysteresis) value in the ON-OFF mode of the ESM-XX20 series controller?
Press and hold the "PSET" button for 5 seconds while on the work screen. Press the "ASET" button while the "ProG" is displayed. Come to the "Cont" parameter with the up / right direction button and press the "ASET" button. Select relay / SSR from “Cout” parameter and press “ASET” button. Select "HEAt / Cool" from the "PrtS" parameter and press the "ASET" button. Select "on-off" from the "CntS" parameter and press the "ASET" button. Enter the subset value as "hysteresis" into the "HYSt" parameter and press the "ASET" button. . You can switch to the working screen by pressing the PSET button 2 times.
Is there 4-20ma output as standard in ESM-4450?
4-20ma output is not standard in the device, it is optional, 4-20ma (emo-430) output module should be installed instead of the module of the device if needed.
How is PID automatic calculation done in ESM-XX50 process control series?
Enter the Set value you want to fix. Then, enter the "run List" parameter in the operator menu and continue with the "tunn" parameter "Atun". The “Attn” parameter will come and you set the value to “YES” to start the automatic tune operation. The "AT" led of the operation screen will light. NOTE: Your set point should be 5% below the full scale from the process value. Otherwise, automatic tune operation cannot be started.
How to make motorized valve control in ESM-XX50 process control series?
By entering “run list” parameter from operator parameters menu. Here you can activate the motor valve control by selecting the "ULSL" parameter according to your process, by selecting "HEAt" or "COOL".
How is step control performed in the ESM-XX50 process control series?
From the operator parameters menu, the number of steps, the temperature and duration of the steps are entered from the rmP SoA parameter.
How is the input-output module installed in the ESM-XX50 process control series?
Remove the back casing of the device from the nails attached to the device. Place your module in the module-1 or module-2 section at the back. Care should be taken to place the "UP" text on the module above.
How to adjust the ESM-XX50 process control series input-output module settings?
If your module is installed or you installed it, “IoP1” parameter will appear in Technician menu parameters. Your settings are made from this section.
I do 8-step ramp temperature control with the ESM-XX50 series device. Can you start from the outside?
ESM-9950 series device is connected to any of the Module1 or Module 2 sockets by connecting the button with the EMI-900 Digital input module and is started from the outside.
Is there a document with modbus addresses and parameters for ESM-XX50 and ESM-XX00 series
Yes, our document is available in English and Turkish.
With which devices can I provide motorized valve control?
You can provide motorized valve control with ESM-XX50 series devices, you can choose with relay or analog control.
I want to make measurement in mt unit on EZM-4430 series device, how can I do?
Coefficients can be entered from the coEFF parameter.
Encoder does not show correct measurement, what should I do?
If you calculate the multiplication coefficient 1 / (Actual measurement value) from the parameters of EZM-XX50 and EZM-XX30 series devices, it will make the correct calculation.
Moisture sensors How many streams can I use?
Can be used up to a maximum temperature of 80 ° C, the sensor will damage if the temperature is exceeded.
Can I shorten or extend the PMI-P sensor cable?
We can shorten the sensor cable by cutting it, but we do not recommend a good addition to the extension, since there will be a loss of communication if it is long, we can extend the cable by looking at our other model sensor types.
What type of temperature sensor should I choose?
You can provide a temperature sensor that adapts to the controller, taking into account the maximum possible temperature. For detailed information, you can contact our Customer representative.
How do I connect the PT-100 3 pin sensors to the ground with 2 inputs?
You can combine 2 wires of the same color and put them into one eye, you can also use the 2-wire PT-100s by bridging the ground with 3 entries.
I want to turn my generator into automatic. Which panel can we use?
It may vary according to the number of inputs and outputs in your generator application.
Trans-AMF, Trans-MidiAMF, Trans-MiniAMF products can be used.
What is the difference between Trans-AMF, Trans-MidiAMF and Trans-MiniAMF products?
In general, all 3 products are Automatic Generator Control and Transfer Panels. However, the panel sections are different from each other.
The largest product is called Trans-AMF, the medium product is MidiAMF and the small product is MiniAMF.
This size difference brought a decrease in the number of entries and exits.
Trans-AMF: 7x Digital Input, 4x Transistor 2x Relay Output
Trans-MidiAMF: 5x Digital Input, 6x Transistor Output
Trans-MiniAMF: 3x Digital Input, 6x Transistor Output
What is the difference between AMF and AUTO series?
AMF series products have network control and transfer.
There is no network measurement and transfer in AUTO series products.
Because of this, it provides a price advantage compared to AMF devices.
What is the difference between Trans-Key and Trans-Crank?
In Trans-KEY device, cranking is done by pressing the button. The device prints the starter and automatically cuts the starter when the running information comes. At the same time, the generator can be started by activating the remote input by selecting one of the Trans-Key device inputs as remote start.
In the Trans-Crank device, the starter is given manually and cut manually again.
Trans-AMF generator does not start when mains is cut.
1) Make sure that the mains light is not illuminated on the front of the Trans-AMF. If this light is on, the device will accept the mains and will not work.
2) Any of the inputs may be selected as "Remote start".
3) Generator working schedule may be activated
4) Technician Department> Network> Actions> Network Fault Detection parameter should be "Active".
Trans-AMF does not read oil pressure.
1) Check the connection of the oil pressure sensor tips.
2) Check if the malfunction and indicator ends of the oil pressure sensor are connected to the correct ends in the Trans-AMF device.
3) Check that the "Technician Department> Inlets> Sender Inlets> Oil pressure inlet type" parameter is selected correctly.
Trans-AMF does not see the network.
1) Check that the Technician Department> System> Network> Phase Selection parameter is selected correctly.
2) Check if the voltage coming to the Trans-AMF and the measured voltage is within the lower and upper limits determined in the "Technician Section> Network> Volt Level" parameter.
3) Check if the frequency measured in the Trans-AMF is within the lower and upper limits determined in the "Technician Section> Network> Frequency" Level parameter.
Does Trans-AMF control the heater?
Depending on the temperature value it receives from the temperature sensor, it can be checked according to the values entered in "Technician Section> Inputs> Sender Inputs> Heater control On and Heater control Off" parameters. For this, any of the outputs should be selected as "128- Heater Control".
Can Trans-AMF output functions be changed?
The outputs of the device are 138 pcs. It has a function. It can be selected from Technician Department> Outputs> Function parameter. Normally Open or Closed can be selected from Polarity parameter.
Trans-AMF does not crank.
Check the starter output of the Trans-AMF device. If the Trans-AMF gives the starter output but does not start, check if the starter relays pull and if the starter motor is energized.
Trans-AMF gives start failure.
Check the starter output of the Trans-AMF device. If the Trans-AMF gives the starter output but does not start, check if the starter relays pull and if the starter motor is energized.
Trans-AMF does not crank, gives oil pressure and speed failure.
When the Trans-AMF device sees the generator running, it starts to check the faults after it passives the starter output and counts the failure delay time. The generator may have turned on the oil pressure sensor before full operation, the charge generator may have generated voltage. In this case, the generator decides that the generator is running before it starts and starts to check the malfunctions.
Is Trans-AMF operated by remote button?
When any of the configurable inputs is selected as "Remote Start", the Trans-AMF device will wait for the Remote start input to be active to start the generator when the mains is disconnected.
Does the Trans-AMF device start the generator when the mains is interrupted at the desired time interval?
In the "Technician Department> Generator> Work Schedule" parameter, the Start and Stop parameters can be entered daily and it can be operated within the desired time interval. In order to perform this operation correctly, the date and time parameters of the Trans-AMF must be set correctly.
Can Trans-AMF control electronic motor?
Trans-AMF's standard features include the Canbus J1939 feature.
Can Trans-AMF refuel?
Any of the outputs can be refueled according to the values entered in the "Technician Department> Inputs> Sender Inputs> Konf.AG1 Control On and OFF parameters by selecting" 42-Configurable Analog Input-1 Control ".
Can Trans-AMF device control motor switch?
Motor switch can be controlled by selecting in "Technician Department> System> Contactors" parameter.
I want to turn my generator into automatic. Which panel can we use?
It may vary according to the number of inputs and outputs in your generator application.
Trans-AMF, Trans-MidiAMF, Trans-MiniAMF products can be used.
What is the difference between Trans-AUTO, Trans-MidiAUTO and Trans-MiniAUTO products?
Generally, all 3 products are Automatic Generator Control Panel. However, the panel sections are different from each other.
The largest product is called Trans-AUTO, the medium product is MidiAMF and the small product is MiniAUTO.
This size difference brought a decrease in the number of entries and exits.
Trans-AUTO: 7x Digital Input, 4x Transistor 2x Relay Output
Trans-MidiAUTO: 5x Digital Input, 6x Transistor Output
Trans-MiniAUTO: 3x Digital Input, 6x Transistor Output.
What is the difference between Trans-MiniAUTO and Trans-MiniAUTO ++.
In Trans-MiniAUTO device, 1x phase generator voltage and 1x phase load current are
measured in Trans-MiniAUTO ++ device, 3x phase generator voltage and 3x phase load current
measurements. There is no difference in the number of digital inputs and outputs between the products.
Which panel should I use to synchronize 2 generators?
By using the Trans-SYNCRO panel, 2 or more generators
can be operated synchronously and automatic load sharing can be realized.
Can we run our existing generators synchronously and switch smoothly with the network?
Automatic load sharing can be performed by running 2 or more generators synchronously using the Trans-SYNCRO panel. In addition, with the Trans-MAINS device to be used as many as the number of networks in the system, the generator network transition can be realized as intermittent, uninterrupted, smooth transition.
The maximum number of meters of CanOPEN line used in generator synchronous panels.
It varies according to the communication speed between the devices.
It is max 250 meters for 250K communication